F61KB Liquid Flow Switches are single-Pole, Double-Throw(SPDT) flow switches that are used in liquid lines carrying water, ethylene glycol, or other liquids not classified as hazardous. They can be wired to energize one device and de-energize another device powered from the same source when liquid flow either exceeds or drops below the set flow rate.
Max. Liquid Pressure |
150 Psig(1034 kPa) |
|||
Min. Liquid Temp |
0℃(32℉) |
|||
Max. Liquid Temp |
120℃(250℉) |
|||
Voltage |
120Vac |
208 Vac |
240 Vac |
277 Vac |
Horsepower |
1 |
1 |
1 |
- |
Full Load Amperes |
16.0 |
8.8 |
8.0 |
- |
Locked Rotor Amperes |
96.0 |
52.8 |
48.0 |
|
Non-inductive Amperes |
16.0 |
16.0 |
16.0 |
16.0 |
Pilot Duty |
125 VA at 24/277/Vac |
|||
Wiring Connection |
Screw Type Terminals |
|||
Pipe Connector |
NPT Threads |